DET-RPM-RAP-FC05
9948 - 9945 - Restart RPM - Decision, Notes: 9946
9947 - Reminder : Start troubleshooting with the control pillar. If both gamma channels s...
Type
Reminder
Start troubleshooting with the control pillar. If both gamma channels show the same issue, check shared parts. If different, troubleshoot separately
9945 - Restart RPM
Restart RPM
Yes
Step Reference Number
01
9944 - 9941 - Measure discriminator voltages - Decision, Notes: 9942
9940 - 9937 - Measure gamma high voltage - Decision, Notes: 9938
9937 - Measure gamma high voltage
Measure gamma high voltage
9936 - 9933 - Adjust gamma high voltage - Decision, Notes: 9934
9933 - Adjust gamma high voltage
Adjust gamma high voltage
9932 - 9930 - Perform an Electronic Alignment - Formal Procedure, Notes: 9007
9930 - Perform an Electronic Alignment
Perform an Electronic Alignment
Step Reference Number
05
9928 - 8168 - Did this fix the problem? - Decision, Notes:
9923 - 9921 - Gently wiggle BNC connectors - Decision, Notes: 9922
9921 - Gently wiggle BNC connectors
Gently wiggle BNC connectors
9098 - 9096 - Replace SCA-774 Board - Formal Procedure, Notes: 9007
9914 - 9910 - Gently wiggle signal cable - Decision, Notes: 9911
9910 - Gently wiggle signal cable
Gently wiggle signal cable
9892 - 9851 - Replace affected signal cable - Decision, Notes: 9852
5882 - 545 - Contact Technical Support - Incomplete, Notes: 5881
9889 - 9884 - Swap signal cables at SCA-774 board - Decision, Notes: 9885
9873 - Note : Be sure to return all cables and connectors to their correct positions at the...
Type
Note
Be sure to return all cables and connectors to their correct positions at the end of troubleshooting and repair effort
9884 - Swap signal cables at SCA-774 board
Swap signal cables at SCA-774 board
9864 - 9861 - Replace VD-580 - Formal Procedure, Notes: 9862
9861 - Replace VD-580
Replace VD-580
Step Reference Number
14
9853 - 9851 - Replace affected signal cable - Decision, Notes: 9852
9848 - 9846 - GH or GL? - Decision, Notes: 9847
9845 - 9843 - Light Leak? - Decision, Notes: 9844
11597 - Note : It is unlikely that the gamma detector would need to be replaced. ...
Type
Note
It is unlikely that the gamma detector would need to be replaced.
9843 - Light Leak?
Light Leak?
Yes
Step Reference Number
17
9842 - 9840 - Replace gamma detector - Formal Procedure, Notes: 9007
9840 - Replace gamma detector
Replace gamma detector
Step Reference Number
18
9905 - 9898 - Reset ULD/LLD - Decision, Notes: 9899
9898 - Reset ULD/LLD
Reset ULD/LLD
Yes
9874 - 9869 - Swap SC-770 controller connectors - Decision, Notes: 7236
9873 - Note : Be sure to return all cables and connectors to their correct positions at the...
Type
Note
Be sure to return all cables and connectors to their correct positions at the end of troubleshooting and repair effort
9869 - Swap SC-770 controller connectors
Swap SC-770 controller connectors
Step Reference Number
20
Note
9858 - 8168 - Did this fix the problem? - Decision, Notes:
9857 - 9855 - Replace High Voltage Board - Formal Procedure, Notes: 9007
9855 - Replace High Voltage Board
Replace High Voltage Board
Step Reference Number
22
8823 - 8168 - Did this fix the problem? - Decision, Notes:
9095 - 9093 - Replace SC-771 Controller Board - Formal Procedure, Notes: 9007
Flowchart Title