DET-RPM-RAP-FC07
5882 - 545 - Contact Technical Support - Incomplete, Notes: 5881
8823 - 8168 - Did this fix the problem? - Decision, Notes:
9095 - 9093 - Replace SC-771 Controller Board - Formal Procedure, Notes: 9007
9093 - Replace SC-771 Controller Board
Replace SC-771 Controller Board
10086 - 10084 - Replace Banner IR Occupancy Sensor - Formal Procedure, Notes: 9007
10091 - Note : Take care that you replace the barrel sensor with the appropriate spare. Blac...
Type
Note
Take care that you replace the barrel sensor with the appropriate spare. Black with black, yellow with yellow, and verify the label indicates that it is a receiver or transmitter, and that model numbers match.
10592 - Note : It would be extremely unlikely for both IR Occupancy sensor pairs to be fault...
Type
Note
It would be extremely unlikely for both IR Occupancy sensor pairs to be faulty at the same time. Recheck the sensor functionality and wiring carefully before deciding to replace IR occupancy sensors.
10084 - Replace Banner IR Occupancy Sensor
Replace Banner IR Occupancy Sensor
10092 - 10087 - Troubleshoot control pillar - Decision, Notes: 10088
10087 - Troubleshoot control pillar
Troubleshoot control pillar
Yes
10099 - 10096 - OUT LEDs on Nanocontroller illuminated? - Decision, Notes: 10097
10096 - OUT LEDs on Nanocontroller illuminated?
OUT LEDs on Nanocontroller illuminated?
10106 - 10103 - Troubleshoot auxiliary pillar - Decision, Notes: 10104
10107 - 8168 - Did this fix the problem? - Decision, Notes:
10110 - 9121 - Measure occupancy input voltage - Decision, Notes: 9041
9121 - Measure occupancy input voltage
Measure occupancy input voltage
~0 VDC [Occupied]
~3.5 VDC [Not Occupied]
10112 - 9099 - Measure occupancy output voltage - Decision, Notes: 9041
9099 - Measure occupancy output voltage
Measure occupancy output voltage
~1.2 VDC [Occupied]
~3.5 VDC [Not Occupied]
10114 - 9121 - Measure occupancy input voltage - Decision, Notes: 9041
9121 - Measure occupancy input voltage
Measure occupancy input voltage
~1.2 VDC [Occupied]
~3.5 VDC [Not Occupied]
10115 - 9121 - Measure occupancy input voltage - Decision, Notes: 9041
9121 - Measure occupancy input voltage
Measure occupancy input voltage
~0 VDC [Occupied]
~3.5 VDC (Not Occupied]
10116 - 9099 - Measure occupancy output voltage - Decision, Notes: 9041
9099 - Measure occupancy output voltage
Measure occupancy output voltage
~1.2 VDC [Occupied]
~3.5 VDC [Not Occupied]
10117 - 8168 - Did this fix the problem? - Decision, Notes:
10119 - 9111 - OCCUPIED on SC-770 Controller? - Decision, Notes: 9109
9111 - OCCUPIED on SC-770 Controller?
OCCUPIED on SC-770 Controller?
10122 - 9113 - Establish Initial conditions - Process, Notes: 9115
9113 - Establish Initial conditions
Establish Initial conditions
Flowchart Title
Vehicle and Rail Monitor Constant Occupancy