9126 - 9099 - Measure occupancy output voltage - Decision, Notes: 9041

9099 - Measure occupancy output voltage

Measure occupancy output voltage
~1.2 VDC [Occupied]
Go to
9125 - 9121 - Measure occupancy input voltage - Decision, Notes: 9041
~3.5 VDC [Not Occupied]
Go to
9098 - 9096 - Replace SCA-774 Board - Formal Procedure, Notes: 9007
Note
9041 - Using a digital multimeter in DC mode,
9100 - measure the occupancy signal output voltage from the Control...
9102 - What is the measured voltage?