9099 - Measure occupancy output voltage Measure occupancy output voltage ~1.2 VDC (Occupied) Go to 10575 - 9121 - Measure occupancy input voltage - Decision, Notes: 9041 ~3.5 VDC (Not Occupied) Go to 10563 - 9096 - Replace SCA-774 Board - Formal Procedure, Notes: 9007 Note 9041 - Using a digital multimeter in DC mode,verify 15 VDC at TB1 pins 1, 2, and 3. 9100 - measure the occupancy signal output voltage from the Control... 9102 - What is the measured voltage?