10573 - 10570 - +15 VDC present at IR sensors? - Decision, Notes: 9041

10606 - Note : In rare cases, the IR receivers are installed in the auxiliary pillar, and em...

Type
Note

In rare cases, the IR receivers are installed in the auxiliary pillar, and emitters in the control pillar. Spare wires in the crossover cable are used to send the occupancy signal to the nanocontroller.

10570 - +15 VDC present at IR sensors?

+15 VDC present at IR sensors?
Yes
Go to
10569 - 10565 - Are Nanocontroller input voltages correct? - Decision, Notes: 10566
No
Go to
9083 - 8997 - Start - Begin, Notes:
Note
9041 - Using a digital multimeter in DC mode,verify 15 VDC at TB1 pins 1, 2, and 3.
10571 - Verify +15 VDC is applied to all sensors: Vehicle Monitor:
10572 - Is +15 VDC present at all sensors?