DET-RPM-RAP-FC02
5882 - 545 - Contact Technical Support - Incomplete, Notes: 5881
8823 - 8168 - Did this fix the problem? - Decision, Notes:
9105 - 9104 - What Occupancy sensor is currently installed? - Decision, Notes:
9104 - What Occupancy sensor is currently installed?
What Occupancy sensor is currently installed?
Wizard Dual Technology sensor
Step Reference Number
04
9089 - 9087 - Replace Spy-2 with IXIO-DT1 - Formal Procedure, Notes: 9007
9092 - 9090 - Wizard Dual Technology sensor replacement - Process, Notes: 9091
9090 - Wizard Dual Technology sensor replacement
Wizard Dual Technology sensor replacement
Step Reference Number
11
9086 - 9084 - Replace IXIO-DT1 Occupancy Sensor - Formal Procedure, Notes: 9007
9095 - 9093 - Replace SC-771 Controller Board - Formal Procedure, Notes: 9007
9098 - 9096 - Replace SCA-774 Board - Formal Procedure, Notes: 9007
9125 - 9121 - Measure occupancy input voltage - Decision, Notes: 9041
9121 - Measure occupancy input voltage
Measure occupancy input voltage
~1.2 VDC [Occupied]
~3.5 VDC [Not Occupied]
9126 - 9099 - Measure occupancy output voltage - Decision, Notes: 9041
9099 - Measure occupancy output voltage
Measure occupancy output voltage
~1.2 VDC [Occupied]
~3.5 VDC [Not Occupied]
9128 - 9121 - Measure occupancy input voltage - Decision, Notes: 9041
9121 - Measure occupancy input voltage
Measure occupancy input voltage
~0 VDC [Occupied]
~3.5 VDC [Not Occupied]
9134 - 9132 - +15 VDC supplied to occupancy sensor? - Decision, Notes: 9115
Flowchart Title
Pedestrian Monitor Will Not Occupy