10569 - 10565 - Are Nanocontroller input voltages correct? - Decision, Notes: 10566

10565 - Are Nanocontroller input voltages correct?

Are Nanocontroller input voltages correct?
Yes
Go to
10564 - 10093 - Replace Nanocontroller - Formal Procedure, Notes: 9007
No
Go to
10086 - 10084 - Replace Banner IR Occupancy Sensor - Formal Procedure, Notes: 9007
Note
10566 - When occupied, voltages should be +15 VDC
9041 - Using a digital multimeter in DC mode,
10567 - Measure the voltages at the Nanocontroller inputs I1 and I2
10568 - Are both input voltages +15 VDC?